EPA Section 608 Core Practice Test (Unofficial)
Practice Section 608 Core topics with original single-choice items mapped to EPA's public test-topics list and 40 CFR Part 82 Subpart F. This bank is unofficial and is not affiliated with the U.S. Environmental Protection Agency. It does not reproduce official exam items.
- Questions: 40 multiple choice, each with an explanation.
- Based on: Unofficial practice only; not affiliated with the U.S. EPA. This bank does not reproduce official exam items.
- Affiliation: Unofficial. Not affiliated with any exam board, agency or state.
- Last reviewed: 2026-11-14.
All 40 questions with answers
Try each question first, then open the answer. To practice them as a timed quiz with a score and a mistake list, use the practice test.
1. According to EPA's Section 608 Core test topics, what happens when chlorofluorocarbon (CFC) molecules reach the stratosphere?
Show answer
Answer: C. Strong ultraviolet light breaks them down and they release chlorine atoms that deplete the ozone layer
EPA states that CFCs are very stable in the troposphere, move to the stratosphere, and are broken down by strong ultraviolet light, where they release chlorine atoms that then deplete the ozone layer. A assigns ozone loss to fluorine, B assigns it to carbon fragments, and D assigns it to intact molecules; the cited account instead identifies chlorine atoms released by UV breakdown.
2. Which statement matches EPA's description of hydrochlorofluorocarbon (HCFC) refrigerants?
Show answer
Answer: D. They contain chlorine and thus deplete stratospheric ozone, but to a much lesser extent than CFCs
EPA defines an HCFC as a compound of hydrogen, chlorine, fluorine, and carbon. HCFCs contain chlorine and thus deplete stratospheric ozone, but to a much lesser extent than CFCs, with ODPs generally ranging from 0.01 to 0.1. A reverses the relative ozone impact, B describes the HFC composition, and C assigns a uniform CFC-11 ODP; the cited definition identifies chlorine-containing HCFCs with substantially lower ODP than CFCs.
3. EPA's Core test topics ask technicians to classify common refrigerants by family. Which pairing is correct?
Show answer
Answer: A. R-12 is a CFC, R-22 is an HCFC, and R-134a is an HFC
EPA's Core topics say identification is by family, not chemical formulas, and give the idea that R-12 is a CFC, R-22 is an HCFC, and R-134 is an HFC.
4. How does EPA describe the ozone-depletion potential (ODP) of CFC, HCFC, and HFC refrigerants?
Show answer
Answer: B. CFCs have higher ODP than HCFCs, and HCFCs have higher ODP than HFCs, which have an ODP of zero
EPA's Core topics state that CFCs have higher ODP than HCFCs, which in turn have higher ODP than HFCs. EPA also states that HFCs do not contain chlorine or bromine and all HFCs have an ozone depletion potential of 0. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Environmental Impacts (ODP comparison and HFC definition): CFCs have higher ODP than HCFCs, and HCFCs have higher ODP than HFCs, which have an ODP of zero; those substitutions fail that cited requirement.
5. Why do hydrofluorocarbon (HFC) refrigerants have an ozone depletion potential of zero, according to EPA?
Show answer
Answer: D. They do not contain chlorine or bromine, so they do not deplete the ozone layer
EPA defines an HFC as a compound of hydrogen, fluorine, and carbon. Because HFCs do not contain chlorine or bromine, they do not deplete the ozone layer, and all HFCs have an ODP of 0. Some HFCs have high global warming potentials. A substitutes complete lower-atmosphere destruction, B proposes chlorine neutralization, and C proposes UV shielding; the cited basis is the absence of chlorine and bromine in HFCs.
6. EPA defines ozone depletion potential (ODP) as a ratio compared with a similar mass of which reference substance?
Show answer
Answer: C. CFC-11, whose ODP is defined as 1.0
EPA defines ODP as the ratio of the impact on ozone of a chemical compared to the impact of a similar mass of CFC-11. The ODP of CFC-11 is defined to be 1.0.
7. Which group does EPA list among the most common chlorofluorocarbon (CFC) substances?
Show answer
Answer: A. CFC-11, CFC-12, CFC-113, CFC-114, and CFC-115
EPA's CFC definition on the Core test-topics page lists the most common CFCs as CFC-11, CFC-12, CFC-113, CFC-114, and CFC-115, with respective ODPs of 1, 1, 0.8, 1, and 0.6. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Environmental Impacts (most common CFCs): CFC-11, CFC-12, CFC-113, CFC-114, and CFC-115; those substitutions fail that cited requirement.
8. What is the Montreal Protocol, as described in EPA's Section 608 Core test topics?
Show answer
Answer: A. The international agreement to phase out production of ozone-depleting substances
EPA's Core topics identify the Montreal Protocol as the international agreement to phase out production of ozone-depleting substances, and as the international treaty governing the protection of stratospheric ozone.
9. Under the U.S. Class I phaseout described by EPA, when did the ban on production and import of CFCs and other Class I ODS, excluding methyl bromide, take effect?
Show answer
Answer: B. January 1, 1996
EPA states that section 604 of the Clean Air Act establishes Class I phaseout targets. The ban on production and import of halons took effect on January 1, 1994. The ban on production and import of other Class I ODS—excluding methyl bromide—took effect on January 1, 1996.
10. According to EPA's U.S. HCFC phaseout schedule, which production and import restriction took effect in 2020?
Show answer
Answer: C. No production or import of HCFC-142b and HCFC-22
EPA's Class II phaseout table lists for 2020: no production or import of HCFC-142b and HCFC-22, meeting a 99.5 percent reduction from baseline. A complete ban on production or import of any HCFCs is listed for 2030. HCFC-141b production and import were already restricted earlier (2003 in the same table). Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in EPA Phaseout of Class II Ozone-Depleting Substances (U.S. HCFC phaseout schedule): No production or import of HCFC-142b and HCFC-22; those substitutions fail that cited requirement.
11. What does 40 CFR 82.154(a) prohibit for a person maintaining, servicing, repairing, or disposing of an appliance?
Show answer
Answer: B. Knowingly venting or otherwise releasing refrigerant from the appliance into the environment, subject to listed exemptions and de minimis releases
Section 82.154(a)(1) states that no person maintaining, servicing, repairing, or disposing of an appliance or industrial process refrigeration may knowingly vent or otherwise release into the environment any refrigerant from such appliances. Listed substitutes in listed end-uses are exempt, and de minimis releases associated with good-faith recovery or recycling are not subject to the prohibition. EPA's Section 608 overview also states that the program prohibits intentionally venting ODS refrigerants and their substitutes, such as HFCs. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.154(a) venting prohibition; EPA Section 608 overview: Knowingly venting or otherwise releasing refrigerant from the appliance into the environment, subject to listed exemptions and de minimis releases; those substitutions fail that cited requirement.
12. Which substitutes does 40 CFR 82.154(a)(1) exempt from the venting prohibition and from Subpart F requirements when used in any application?
Show answer
Answer: C. Carbon dioxide, nitrogen, and water
Section 82.154(a)(1)(i)–(iii) exempt carbon dioxide, nitrogen, and water in any application. Other exemptions are narrower (for example, ammonia in commercial or industrial process refrigeration or in absorption units, and certain hydrocarbons only in specified end-uses). Common HFC and CFC/HCFC refrigerants are not listed as generally exempt.
13. When are refrigerant releases treated as de minimis and therefore not subject to the venting prohibition in 40 CFR 82.154?
Show answer
Answer: C. When they are associated with good-faith attempts to recycle or recover refrigerants and the applicable Subpart F practices and certified equipment are used
Section 82.154(a)(2) states that de minimis releases associated with good-faith attempts to recycle or recover refrigerants are not subject to the venting prohibition. Except for exempt substitutes, releases are de minimis only if the applicable practices in §§ 82.155, 82.156, and (where applicable) 82.157 are observed, certified recovery or recycling machines are used, technician certification in § 82.161 is observed, and reclamation requirements in § 82.164 are observed—or the Subpart B MVAC requirements are observed. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.154(a)(2) de minimis releases: When they are associated with good-faith attempts to recycle or recover refrigerants and the applicable Subpart F practices and certified equipment are used; those substitutions fail that cited requirement.
14. EPA has developed four types of Section 608 technician certification. Which description is correct?
Show answer
Answer: B. Type I for small appliances, Type II for high- or very high-pressure appliances (except small appliances and MVACs), Type III for low-pressure appliances, and Universal for all of those types
EPA lists four types: Type I for servicing small appliances; Type II for servicing or disposing of high- or very high-pressure appliances, except small appliances and MVACs; Type III for servicing or disposing of low-pressure appliances; and Universal for servicing all of those types. 40 CFR 82.161(a)(1) uses the same four categories. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Technician Certification Requirements — Types of Certifications; 40 CFR 82.161(a): Type I for small appliances, Type II for high- or very high-pressure appliances (except small appliances and MVACs), Type III for low-pressure appliances, and Universal for all of those types; those substitutions fail that cited requirement.
15. Which statement about Section 608 technician certification is stated on EPA's certification-requirements page?
Show answer
Answer: D. Credentials do not expire, and a Core test taken as an open-book exam is not accepted toward Universal certification
EPA states that Section 608 Technician Certification credentials do not expire. It also states that Core tests taken as an open book exam cannot be used to get Universal Certification; the Core test must be taken as a proctored exam in order to attain Universal Certification. The question stem and options avoid that wording and instead say an open-book Core test is not accepted toward Universal certification. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Technician Certification Requirements: Credentials do not expire, and a Core test taken as an open-book exam is not accepted toward Universal certification; those substitutions fail that cited requirement.
16. When does EPA exempt an apprentice from the Section 608 technician certification requirement?
Show answer
Answer: C. When the apprentice is closely and continually supervised by a certified technician
EPA states that apprentices are exempt from certification requirements provided they are closely and continually supervised by a certified technician. 40 CFR 82.161(a)(2) requires that close and continual supervision while the apprentice performs maintenance, service, repair, or disposal that could reasonably be expected to release refrigerant.
17. Under 40 CFR 82.152, what is a high-pressure appliance?
Show answer
Answer: B. An appliance that uses a refrigerant with a liquid-phase saturation pressure between 170 psia and 355 psia at 104°F, such as R-22, R-407C, or R-410A
Section 82.152 defines a high-pressure appliance as one that uses a refrigerant with a liquid-phase saturation pressure between 170 psia and 355 psia at 104°F. Examples include but are not limited to appliances using R-22, R-407A, R-407C, R-410A, and R-502. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 definition of high-pressure appliance: An appliance that uses a refrigerant with a liquid-phase saturation pressure between 170 psia and 355 psia at 104°F, such as R-22, R-407C, or R-410A; those substitutions fail that cited requirement.
18. Under 40 CFR 82.152, which refrigerants are listed as examples used in low-pressure appliances?
Show answer
Answer: A. R-11, R-123, R-113, and R-245fa, which have a liquid-phase saturation pressure below 45 psia at 104°F
A low-pressure appliance uses a refrigerant with a liquid-phase saturation pressure below 45 psia at 104°F. Examples include but are not limited to R-11, R-123, R-113, and R-245fa. The other groups are the official examples for high-pressure, medium-pressure, and very high-pressure appliances. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 definition of low-pressure appliance: R-11, R-123, R-113, and R-245fa, which have a liquid-phase saturation pressure below 45 psia at 104°F; those substitutions fail that cited requirement.
19. Which pairing correctly matches 40 CFR 82.152 pressure categories?
Show answer
Answer: D. R-134a is listed as a medium-pressure example, and R-23 is listed as a very high-pressure example
A medium-pressure appliance uses a refrigerant with liquid-phase saturation pressure between 45 psia and 170 psia at 104°F; examples include R-114, R-124, R-12, R-134a, and R-500. A very high-pressure appliance uses a refrigerant with a critical temperature below 104°F or a liquid-phase saturation pressure above 355 psia at 104°F; examples include R-13, R-23, R-503, R-508A, and R-508B.
20. What is a small appliance under 40 CFR 82.152?
Show answer
Answer: D. An appliance fully manufactured, charged, and hermetically sealed in a factory with five pounds or less of refrigerant
Section 82.152 defines a small appliance as any appliance that is fully manufactured, charged, and hermetically sealed in a factory with five (5) pounds or less of refrigerant, including but not limited to household refrigerators and freezers, room air conditioners, dehumidifiers, under-the-counter ice makers, vending machines, and drinking water coolers. EPA's definitions page uses the same five-pound factory-sealed test. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 and EPA Definitions of Section 608 Terms — small appliance: An appliance fully manufactured, charged, and hermetically sealed in a factory with five pounds or less of refrigerant; those substitutions fail that cited requirement.
21. How does 40 CFR 82.152 distinguish self-contained recovery equipment from system-dependent recovery equipment?
Show answer
Answer: B. Self-contained equipment can remove refrigerant without assistance from components in the appliance; system-dependent equipment requires that assistance
Self-contained recovery equipment is capable of removing the refrigerant from an appliance without the assistance of components contained in the appliance. System-dependent recovery equipment requires the assistance of components contained in an appliance to remove the refrigerant from the appliance. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 definitions of self-contained and system-dependent recovery equipment: Self-contained equipment can remove refrigerant without assistance from components in the appliance; system-dependent equipment requires that assistance; those substitutions fail that cited requirement.
22. What does it mean to recover refrigerant under Section 608?
Show answer
Answer: A. To remove refrigerant in any condition from an appliance and store it in an external container without necessarily testing or processing it
EPA and 40 CFR 82.152 define recover as removing refrigerant in any condition from an appliance and storing it in an external container without necessarily testing or processing it in any way. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 and EPA Recovering, Recycling, and Reclaiming of Refrigerants — Recover: To remove refrigerant in any condition from an appliance and store it in an external container without necessarily testing or processing it; those substitutions fail that cited requirement.
23. What does recycle mean when referring to refrigerant under Subpart F?
Show answer
Answer: D. To extract refrigerant from an appliance (except MVACs) and clean it for reuse in equipment of the same owner without meeting all reclamation requirements
Recycle, when referring to refrigerant, means to extract refrigerant from an appliance (except MVACs) and clean it for reuse in equipment of the same owner without meeting all of the requirements for reclamation. In general, recycled refrigerant is cleaned using oil separation and passes through devices such as replaceable core filter-driers. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 and EPA Recovering, Recycling, and Reclaiming of Refrigerants — Recycle: To extract refrigerant from an appliance (except MVACs) and clean it for reuse in equipment of the same owner without meeting all reclamation requirements; those substitutions fail that cited requirement.
24. What must be done for recovered refrigerant to be reclaimed under 40 CFR 82.152?
Show answer
Answer: B. It must be reprocessed to the applicable specifications in appendix A (based on AHRI Standard 700-2016) and verified by the prescribed analytical methodology
Reclaim means to reprocess recovered refrigerant to all of the specifications in appendix A of Subpart F (based on AHRI Standard 700-2016) that apply to that refrigerant and to verify that the refrigerant meets those specifications using the analytical methodology prescribed in section 5 of appendix A. EPA's Core topics also list the standard for reclaimed refrigerant as AHRI Standard 700-2016. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.152 Reclaim; EPA Core test topics (AHRI Standard 700-2016): It must be reprocessed to the applicable specifications in appendix A (based on AHRI Standard 700-2016) and verified by the prescribed analytical methodology; those substitutions fail that cited requirement.
25. Under EPA's refrigerant sales restriction, who is responsible for verifying a technician's certification before a sale?
Show answer
Answer: B. The seller of the refrigerant, meaning the person or entity selling, distributing, or offering refrigerant for sale or distribution
EPA states that the seller of the refrigerant is responsible for verifying that the buyer either is a certified technician or employs a certified technician. By seller, EPA means the person or entity selling, distributing, or offering refrigerant for sale or distribution. Where more than one entity acts as seller or distributor, all are responsible. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Questions and Answers about the Refrigerant Sales Restriction: The seller of the refrigerant, meaning the person or entity selling, distributing, or offering refrigerant for sale or distribution; those substitutions fail that cited requirement.
26. What sales records must refrigerant vendors keep, and for how long, according to EPA?
Show answer
Answer: D. Invoices showing the purchaser's name, the date of sale, and the quantity purchased, kept for three years from the date of sale
EPA states that refrigerant vendors must maintain invoices that indicate the name of the purchaser, the date of sale, and the quantity of refrigerant purchased. The record does not need to include the technician's certification number. These records must be kept for three years from the date of sale. If someone other than the technician completes the transaction, the seller must also keep documentation that the buyer employs at least one certified technician. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in EPA Questions and Answers about the Refrigerant Sales Restriction — records sellers must keep: Invoices showing the purchaser's name, the date of sale, and the quantity purchased, kept for three years from the date of sale; those substitutions fail that cited requirement.
27. May used refrigerant be sold for use in an appliance if it has not been reclaimed?
Show answer
Answer: D. EPA prohibits the sale of used refrigerant for use in an appliance unless that refrigerant has been reclaimed by an EPA-certified reclaimer
EPA states that it prohibits the sale of used refrigerant for use in an appliance unless that refrigerant has been reclaimed by an EPA-certified reclaimer. A technician may charge used refrigerant recovered from an appliance into another appliance owned by the same customer, but selling it to others requires reclamation. This is also restated in EPA's technician Q&A. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in EPA Questions and Answers about the Refrigerant Sales Restriction; EPA technician Q&A: EPA prohibits the sale of used refrigerant for use in an appliance unless that refrigerant has been reclaimed by an EPA-certified reclaimer; those substitutions fail that cited requirement.
28. What do EPA's Core test topics state about so-called drop-in replacement refrigerants?
Show answer
Answer: A. There is an absence of drop-in replacements
EPA's Core topics under Substitute Refrigerants and oils include the absence of drop-in replacements, along with lubricant incompatibility and blend fractionation. Type 2 topics separately note that hydrocarbons are not approved for retrofits. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Substitute Refrigerants and oils: There is an absence of drop-in replacements; those substitutions fail that cited requirement.
29. Which lubricant pairing is given in EPA's Core test topics?
Show answer
Answer: B. Esters with R-134a, and alkylbenzenes for HCFCs
EPA's Core topics note the incompatibility of substitute refrigerants with many lubricants used with CFC and HCFC refrigerants, and include identification of lubricants for given refrigerants, such as esters with R-134 and alkylbenzenes for HCFCs.
30. What fractionation problem do EPA's Core test topics expect technicians to understand?
Show answer
Answer: C. The tendency of different components of blends to leak at different rates
EPA's Core topics list the fractionation problem as the tendency of different components of blends to leak at different rates.
31. Which practice and which recovery-speed factors are listed in EPA's Core recovery-technique topics?
Show answer
Answer: A. Avoid mixing refrigerants; speed is affected by ambient temperature, the size of the recovery or recycling equipment, and hose length and diameter
EPA's Core Recovery Techniques topics include the need to avoid mixing refrigerants and the factors affecting speed of recovery (ambient temperature, size of recycling or recovery equipment, hose length and diameter, and so on). Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Recovery Techniques: Avoid mixing refrigerants; speed is affected by ambient temperature, the size of the recovery or recycling equipment, and hose length and diameter; those substitutions fail that cited requirement.
32. Why do EPA's Core test topics say a system should be evacuated at the end of service?
Show answer
Answer: C. To eliminate air and moisture
EPA's Core Dehydration Evacuation topic is the need to evacuate the system to eliminate air and moisture at the end of service.
33. For appliances with a full charge of 50 or more pounds of refrigerant, which leak rates does 40 CFR 82.157(c)(2) set?
Show answer
Answer: B. 20 percent for commercial refrigeration, 30 percent for industrial process refrigeration, and 10 percent for comfort cooling or other covered appliances
Section 82.157(c)(2) sets a 20 percent leak rate for commercial refrigeration equipment, a 30 percent leak rate for industrial process refrigeration equipment, and a 10 percent leak rate for comfort cooling appliances or other appliances with a full charge of 50 or more pounds of refrigerant not covered by those first two categories. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.157(c) leak rates: 20 percent for commercial refrigeration, 30 percent for industrial process refrigeration, and 10 percent for comfort cooling or other covered appliances; those substitutions fail that cited requirement.
34. Which exposure risks and personal protective equipment does EPA list in the Core safety topics?
Show answer
Answer: D. Oxygen deprivation, cardiac effects, frostbite, and long-term hazards; PPE includes gloves, goggles, and self-contained breathing apparatus in extreme cases
EPA's Core Safety topics include risks of exposure to refrigerant (for example, oxygen deprivation, cardiac effects, frost bite, and long-term hazards) and personal protective equipment (gloves, goggles, and self-contained breathing apparatus in extreme cases). Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Safety (exposure risks and PPE): Oxygen deprivation, cardiac effects, frostbite, and long-term hazards; PPE includes gloves, goggles, and self-contained breathing apparatus in extreme cases; those substitutions fail that cited requirement.
35. What do EPA's Core safety topics require technicians to know about refrigerant cylinders?
Show answer
Answer: A. Reusable recovery cylinders must be DOT-approved and follow the yellow-and-gray color code, and disposable cylinders are not to be refilled
EPA's Core Safety topics distinguish reusable (or recovery) cylinders from disposable cylinders: ensure the former are Department of Transportation approved, know the former's yellow and gray color code, and do not refill the latter. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Safety (reusable versus disposable cylinders): Reusable recovery cylinders must be DOT-approved and follow the yellow-and-gray color code, and disposable cylinders are not to be refilled; those substitutions fail that cited requirement.
36. What fill limit do EPA's Core safety topics highlight for refrigerant cylinders?
Show answer
Answer: C. The risks of filling cylinders more than 80 percent full
EPA's Core Safety topics expressly include the risks of filling cylinders more than 80 percent full.
37. How should nitrogen be used for leak detection, according to EPA's Core safety topics?
Show answer
Answer: C. Use nitrogen rather than oxygen or compressed air, and use a pressure regulator and relief valve with the nitrogen
EPA's Core Safety topics include the use of nitrogen rather than oxygen or compressed air for leak detection, and the use of a pressure regulator and relief valve with nitrogen. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in EPA Section 608 Test Topics — Core, Safety (nitrogen leak detection): Use nitrogen rather than oxygen or compressed air, and use a pressure regulator and relief valve with the nitrogen; those substitutions fail that cited requirement.
38. Which labels do EPA's Core shipping topics say are required for refrigerant cylinders?
Show answer
Answer: D. Refrigerant identification and a DOT classification tag
EPA's Core Shipping topic is labels required for refrigerant cylinders (refrigerant identification, DOT classification tag). A substitutes an efficiency label, B substitutes weight and invoice information, and C substitutes a purity certificate for the required refrigerant identity and DOT classification tag.
39. What must a Section 608 certified technician do with a copy of the certificate?
Show answer
Answer: A. Keep a copy at the place of business and maintain a copy until three years after no longer operating as a technician
40 CFR 82.161(a)(3)(i)–(ii) requires technicians certified under that section to keep a copy of their certificate at their place of business and to maintain a copy of their certificate until three years after no longer operating as a technician. EPA's technician Q&A also states that a section 608 certified technician is required to keep a copy of the certification. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.161(a)(3); EPA technician Q&A on keeping a copy of certification: Keep a copy at the place of business and maintain a copy until three years after no longer operating as a technician; those substitutions fail that cited requirement.
40. Under 40 CFR 82.161(a)(1)(vii), which disposal work is outside the Section 608 technician certification requirement?
Show answer
Answer: A. Disposing of small appliances, MVACs, and MVAC-like appliances
Section 82.161(a)(1)(vii) states that persons who dispose of small appliances, MVACs, and MVAC-like appliances are not required to be certified. Persons who maintain, service, or repair those appliances, or who dispose of other appliances that could release refrigerant, remain subject to the applicable certification provisions in § 82.161(a)(1). Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 40 CFR 82.161(a)(1)(vii); EPA technician certification requirements: Disposing of small appliances, MVACs, and MVAC-like appliances; those substitutions fail that cited requirement.
Frequently asked questions
Is this an official exam?
No. These are original, unofficial practice questions written by PocketLearn. They are not released exam items. Unofficial independent study material. Consult official exam resources; not a complete exam review.
How many questions are there?
40 multiple-choice questions. Each question has an explanation.
Is it free?
Yes. You can open the practice set without an account; signing in lets you save progress and review mistakes.
Can I use it on my phone?
It opens in a mobile browser. A laptop or tablet is easier for longer sets.
More free practice tests
- CDL Air Brakes practice test
- CDL General Knowledge practice test
- CDL Combination Vehicles practice test
- CompTIA Security+ SY0-701 practice test
- NCLEX Pharmacology Fundamentals practice test
- NCLEX Pediatrics practice test
- Florida Real Estate Course I Unit 1 practice test
- Life and Health Insurance practice test
- FAA Part 107 Regulations practice test
- NCLEX Respiratory practice test
- CDL Pre-Trip Inspection practice test
- California Real Estate Salesperson Set 2 practice test
- NCLEX Pharmacology: Legal and Ethical Medication Safety practice test
- NCLEX Pharmacology: Antimicrobial Medications practice test
- Florida Real Estate Unit 3 Practice (Unofficial) practice test
- Florida Real Estate Unit 4: Relationships, Duties and Disclosure practice test
- CDL Air Brakes Practice — Set 3 practice test
- New York CDL HazMat Practice — Set 2 practice test
- CompTIA A+ Core 2 Practice Test Set 3 (Unofficial) practice test
- CDL Combination Vehicles Practice Set 2 (Unofficial) practice test
- Journeyman Electrician Basics Practice Test (Unofficial) practice test
- 2025 U.S. civics practice test
- Technician Class (ham radio) practice test