Journeyman Electrician Basics Practice Test (Unofficial)
Practice journeyman basics with original single-choice items mapped to public state exam bulletins and OSHA 29 CFR 1910.303. This bank is unofficial. It is not affiliated with NFPA, TDLR, Minnesota DLI, or OSHA, and it does not reprint National Electrical Code source text.
- Questions: 40 multiple choice, each with an explanation.
- Based on: Unofficial practice only; not affiliated with NFPA, TDLR, Minnesota DLI, or OSHA. This bank does not reproduce official exam items and does not reprint NEC source text.
- Affiliation: Unofficial. Not affiliated with any exam board, agency or state.
- Last reviewed: 2026-11-14.
All 40 questions with answers
Try each question first, then open the answer. To practice them as a timed quiz with a score and a mistake list, use the practice test.
1. According to the Texas Department of Licensing and Regulation journeyman electrician candidate bulletin, how is the scored exam structured?
Show answer
Answer: B. 80 scored items, 240 minutes, and 70 percent correct to pass
The TDLR bulletin's Journeyman Electrician outline states: 80 Scored Items — 240 Minutes — 70% Correct to Pass, plus 5 non-scored items with 20 minutes, and an examination fee of $78. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in TDLR / PSI Candidate Information Bulletin — Journeyman Electrician content outline: 80 scored items, 240 minutes, and 70 percent correct to pass; those substitutions fail that cited requirement.
2. In addition to the 80 scored items, how many non-scored items does the Texas journeyman electrician bulletin list, and how much time is allotted for them?
Show answer
Answer: D. 5 non-scored items and 20 minutes
The bulletin lists 5 Non-Scored Items — 20 Minutes on the Journeyman Electrician outline, separate from the 80 scored items and 240 minutes.
3. Effective October 1, 2023, which reference does the Texas electrician bulletin say the examinations use, and in what format?
Show answer
Answer: C. The examinations are open book and are referenced to the 2023 National Electrical Code
The bulletin states: Effective October 1, 2023, the examinations will be referenced to the 2023 NEC Code Book. It then states that the examinations are OPEN BOOK and that the National Electrical Code, 2023 Edition, is the allowed reference material. Candidates must bring their own NEC book.
4. Which publication does the Texas electrician bulletin say is not allowed in the examination room?
Show answer
Answer: D. The NEC Handbook
The bulletin allows a soft-bound NEC book, and allows highlighting, underlining, and/or notes placed in the book prior to the examination session, as well as permanent publisher index tabs. It expressly states that the NEC HANDBOOK is NOT allowed in the examination room. Loose-leaf, spiral-bound, or ring-bound copies, homemade tabs, and additional paper are also not allowed.
5. Which NEC book condition does the Texas bulletin allow in the examination room?
Show answer
Answer: C. A soft-bound edition, which may already be highlighted or tabbed with permanent publisher index tabs
The bulletin allows any soft-bound edition of the NEC (questions are based on the current TDLR-adopted bound edition). The candidate's book may be highlighted, underlined, and/or contain notes prior to the session, and may be tabbed with permanent index tabs manufactured and/or provided by the NEC book publisher. Loose-leaf, spiral-bound, or ring-bound copies, homemade tabs, and any additional paper are not allowed, and candidates may not mark the book during the session. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in TDLR / PSI Candidate Information Bulletin — What is allowed / not allowed: A soft-bound edition, which may already be highlighted or tabbed with permanent publisher index tabs; those substitutions fail that cited requirement.
6. Unless a Texas journeyman exam question specifically notes otherwise, how are conductors to be considered?
Show answer
Answer: C. All conductors are to be considered copper
The journeyman content outline states: Unless SPECIFICALLY NOTED in the question, all conductors are to be considered copper. The same footnote appears on the other Texas electrician outlines in the bulletin.
7. On the Texas journeyman electrician content outline, which subject area has the most scored items?
Show answer
Answer: A. Electrical Wiring Methods and Electrical Materials, with 18 items
The outline assigns 18 items to Electrical Wiring Methods and Electrical Materials, the largest share. Branch Circuit Calculations and Conductors has 15; Renewable Energy Technologies has 2; Electrical Feeders and Electrical Control Devices and Disconnecting Means have 3 each. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in TDLR / PSI Candidate Information Bulletin — Journeyman Electrician content outline: Electrical Wiring Methods and Electrical Materials, with 18 items; those substitutions fail that cited requirement.
8. How many scored items does the Texas journeyman outline assign to Branch Circuit Calculations and Conductors, and to Electrical Services, Service Equipment, and Separately Derived Systems?
Show answer
Answer: A. 15 items for branch-circuit calculations and conductors, and 9 items for services, service equipment, and separately derived systems
The journeyman outline lists Branch Circuit Calculations and Conductors at 15 items and Electrical Services, Service Equipment, and Separately Derived Systems at 9 items. Other listed counts include Definitions, Calculations, Theory, and Plans (6), Electrical Equipment and Devices (10), Motors and Generators (5), and Special Occupancies, Equipment, and Conditions (9). Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in TDLR / PSI Candidate Information Bulletin — Journeyman Electrician content outline: 15 items for branch-circuit calculations and conductors, and 9 items for services, service equipment, and separately derived systems; those substitutions fail that cited requirement.
9. According to the Minnesota Department of Labor and Industry electrical license examination guide, which code edition is used for the electrical license examination questions, and when did that edition become effective in Minnesota?
Show answer
Answer: B. The 2026 National Electrical Code, which became effective August 17, 2026
The Minnesota DLI guide states that the 2026 National Electrical Code became effective August 17, 2026, and is the code edition used for the questions in the electrical license examinations. It separately states that the lineman license examination is based on the 2023 National Electrical Safety Code.
10. What does the Minnesota electrical license examination guide say about how incorrect choices and negative-response questions are written?
Show answer
Answer: A. Incorrect choices are written to be plausible, and negative-response questions are used only in limited instances
The guide states that incorrect multiple-choice answer selections are plausible, and that questions with a negative-response format such as “which of the following does NOT apply” are used only in limited instances. It also notes that questions may include extraneous information and, unless stated otherwise, assume a unity power factor. B changes limited negative-response use to majority use, C imposes uniform numerical alternatives and section coverage, and D substitutes out-of-outline material and universal negative code lookups for the guide’s plausible alternatives and limited negative-response format.
11. Under 29 CFR 1910.303, which statement about electrical equipment is correct?
Show answer
Answer: A. Conductors and equipment required or permitted by the subpart shall be acceptable only if approved, and listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling
Section 1910.303(a) states that conductors and equipment required or permitted by Subpart S shall be acceptable only if approved, as defined in § 1910.399. Section 1910.303(b)(2) states that listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. A note to (b)(1)(i) adds that suitability may be evidenced by listing or labeling for that identified purpose. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(a) and (b)(2): Conductors and equipment required or permitted by the subpart shall be acceptable only if approved, and listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling; those substitutions fail that cited requirement.
12. What does 29 CFR 1910.303(b)(3) require of completed wiring installations?
Show answer
Answer: C. They shall be free from short circuits and from grounds other than those required or permitted by the subpart
Section 1910.303(b)(3) states: Completed wiring installations shall be free from short circuits and from grounds other than those required or permitted by this subpart. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(3): They shall be free from short circuits and from grounds other than those required or permitted by the subpart; those substitutions fail that cited requirement.
13. What interrupting rating does 29 CFR 1910.303(b)(4) require for equipment intended to interrupt current at fault levels?
Show answer
Answer: A. An interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment
Section 1910.303(b)(4) requires equipment intended to interrupt current at fault levels to have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(4): An interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment; those substitutions fail that cited requirement.
14. Unless identified for use in the operating environment, where does 29 CFR 1910.303(b)(6) say conductors or equipment shall not be located?
Show answer
Answer: D. In damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other deteriorating agents; or where exposed to excessive temperatures
Section 1910.303(b)(6) states that unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(6): In damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other deteriorating agents; or where exposed to excessive temperatures; those substitutions fail that cited requirement.
15. What does 29 CFR 1910.303(b)(7) require for unused openings in boxes, raceways, cabinets, and equipment housings?
Show answer
Answer: C. They shall be effectively closed to afford protection substantially equivalent to the wall of the equipment
Section 1910.303(b)(7) requires electric equipment to be installed in a neat and workmanlike manner. Paragraph (b)(7)(i) requires unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings to be effectively closed to afford protection substantially equivalent to the wall of the equipment. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(7): They shall be effectively closed to afford protection substantially equivalent to the wall of the equipment; those substitutions fail that cited requirement.
16. How does 29 CFR 1910.303(b)(8) address mounting of electric equipment, including wooden plugs in masonry?
Show answer
Answer: D. Electric equipment shall be firmly secured to the surface on which it is mounted, and wooden plugs driven into masonry, concrete, plaster, or similar materials are not considered a secure means of fastening
Section 1910.303(b)(8)(i) requires electric equipment to be firmly secured to the surface on which it is mounted. The note to that paragraph states that wooden plugs driven into holes in masonry, concrete, plaster, or similar materials are not considered secure means of fastening electric equipment. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(8)(i) and its note: Electric equipment shall be firmly secured to the surface on which it is mounted, and wooden plugs driven into masonry, concrete, plaster, or similar materials are not considered a secure means of fastening; those substitutions fail that cited requirement.
17. Under 29 CFR 1910.303(c)(1), when may copper and aluminum conductors be intermixed in a terminal or splicing connector where they make physical contact?
Show answer
Answer: B. Only when the device is identified for the purpose and conditions of use
Section 1910.303(c)(1)(ii) states that conductors of dissimilar metals may not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors (such as copper and aluminum, copper and copper-clad aluminum, or aluminum and copper-clad aluminum) unless the device is identified for the purpose and conditions of use. Pressure terminals must also be identified for the material of the conductor. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(c)(1): Only when the device is identified for the purpose and conditions of use; those substitutions fail that cited requirement.
18. How must a soldered splice be made under 29 CFR 1910.303(c)(3)(i)?
Show answer
Answer: C. It shall first be spliced or joined so it is mechanically and electrically secure without solder, and then soldered, and the joint shall be covered with insulation equivalent to that of the conductors or with an identified insulating device
Section 1910.303(c)(3)(i) requires conductors to be spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be spliced or joined to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors shall be covered with insulation equivalent to that of the conductors or with an insulating device identified for the purpose. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(c)(3)(i): It shall first be spliced or joined so it is mechanically and electrically secure without solder, and then soldered, and the joint shall be covered with insulation equivalent to that of the conductors or with an identified insulating device; those substitutions fail that cited requirement.
19. What does 29 CFR 1910.303(d) require for parts of electric equipment that in ordinary operation produce arcs, sparks, flames, or molten metal?
Show answer
Answer: D. They shall be enclosed or separated and isolated from all combustible material
Section 1910.303(d) states that parts of electric equipment that in ordinary operation produce arcs, sparks, flames, or molten metal shall be enclosed or separated and isolated from all combustible material. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(d): They shall be enclosed or separated and isolated from all combustible material; those substitutions fail that cited requirement.
20. What markings does 29 CFR 1910.303(e) require on electric equipment before it may be used?
Show answer
Answer: C. The manufacturer's name, trademark, or other descriptive marking identifying the organization responsible for the product, and other markings giving voltage, current, wattage, or other ratings as necessary, of sufficient durability for the environment
Section 1910.303(e)(1) says electric equipment may not be used unless it is marked with the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified, and with other markings giving voltage, current, wattage, or other ratings as necessary. Section 1910.303(e)(2) requires the marking to be of sufficient durability to withstand the environment involved. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(e): The manufacturer's name, trademark, or other descriptive marking identifying the organization responsible for the product, and other markings giving voltage, current, wattage, or other ratings as necessary, of sufficient durability for the environment; those substitutions fail that cited requirement.
21. How must disconnecting means and circuits be identified under 29 CFR 1910.303(f)?
Show answer
Answer: B. Each required motor or appliance disconnect, and each service, feeder, and branch circuit at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose unless that purpose is evident, and the marking shall be durable enough for the environment
Section 1910.303(f)(1) requires each disconnecting means required for motors and appliances to be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Section 1910.303(f)(2) requires the same for each service, feeder, and branch circuit at its disconnecting means or overcurrent device. Section 1910.303(f)(3) requires those markings to be of sufficient durability to withstand the environment involved. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(f)(1)–(3): Each required motor or appliance disconnect, and each service, feeder, and branch circuit at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose unless that purpose is evident, and the marking shall be durable enough for the environment; those substitutions fail that cited requirement.
22. What locking capability does 29 CFR 1910.303(f)(4) require for disconnecting means required by Subpart S?
Show answer
Answer: A. They shall be capable of being locked in the open position
Section 1910.303(f)(4) states: Disconnecting means required by this subpart shall be capable of being locked in the open position.
23. For equipment operating at 600 volts, nominal, or less, what minimum width of working space does 29 CFR 1910.303(g)(1)(i)(B) require in front of the equipment?
Show answer
Answer: D. The width of the equipment or 762 mm (30 in.), whichever is greater, and the space shall permit at least a 90-degree opening of equipment doors or hinged panels
Section 1910.303(g)(1)(i)(B) requires the width of working space in front of the electric equipment to be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(i)(B): The width of the equipment or 762 mm (30 in.), whichever is greater, and the space shall permit at least a 90-degree opening of equipment doors or hinged panels; those substitutions fail that cited requirement.
24. Under Table S-1 of 29 CFR 1910.303, what is the minimum depth of clear working space for equipment rated 0–150 volts to ground, for Conditions A, B, and C, on installations built on or after April 16, 1981?
Show answer
Answer: D. 0.9 m (3.0 ft) for Condition A, Condition B, and Condition C
Table S-1 lists, for 0–150 volts to ground, a minimum clear distance of 0.9 m (3.0 ft) under Condition A, Condition B, and Condition C. A footnote allows 0.7 m (2.5 ft) for installations built before April 16, 1981. Distances are measured from the live parts if exposed or from the enclosure front or opening if enclosed. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(i)(A) and Table S-1: 0.9 m (3.0 ft) for Condition A, Condition B, and Condition C; those substitutions fail that cited requirement.
25. Under Table S-1 of 29 CFR 1910.303, what is the minimum depth of clear working space for 151–600 volts to ground under Condition C (exposed live parts on both sides of the work space, with the operator between)?
Show answer
Answer: C. 1.2 m (4.0 ft)
Table S-1 lists 151–600 volts to ground as 0.9 m (3.0 ft) for Condition A, 1.0 m (3.5 ft) for Condition B, and 1.2 m (4.0 ft) for Condition C. Condition C is defined as exposed live parts on both sides of the work space (not guarded as provided in Condition A) with the operator between.
26. Which two working-space rules in 29 CFR 1910.303(g)(1) are correctly stated?
Show answer
Answer: A. The required working space may not be used for storage, and other equipment associated with the electrical installation above or below may extend not more than 153 mm (6 in.) beyond the front of the electric equipment
Section 1910.303(g)(1)(ii) states that working space required by the standard may not be used for storage. Section 1910.303(g)(1)(i)(C) requires the work space to be clear from the grade, floor, or platform to the required height, except that other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 153 mm (6 in.) beyond the front of the electric equipment. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(i)(C) and (g)(1)(ii): The required working space may not be used for storage, and other equipment associated with the electrical installation above or below may extend not more than 153 mm (6 in.) beyond the front of the electric equipment; those substitutions fail that cited requirement.
27. What illumination rule does 29 CFR 1910.303(g)(1)(v) set for indoor working spaces about service equipment, switchboards, panelboards, and motor control centers?
Show answer
Answer: D. Illumination shall be provided, and in electric equipment rooms the illumination may not be controlled by automatic means only
Section 1910.303(g)(1)(v) requires illumination for all working spaces about service equipment, switchboards, panelboards, and motor control centers installed indoors. Additional lighting fixtures are not required where the working space is illuminated by an adjacent light source. In electric equipment rooms, the illumination may not be controlled by automatic means only. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(v): Illumination shall be provided, and in electric equipment rooms the illumination may not be controlled by automatic means only; those substitutions fail that cited requirement.
28. What minimum headroom does 29 CFR 1910.303(g)(1)(vi) require for working spaces about service equipment, switchboards, panelboards, or motor control centers?
Show answer
Answer: B. 1.91 m (6.25 ft) for installations built before August 13, 2007, and 1.98 m (6.5 ft) for installations built on or after that date, except that if the equipment is taller than 1.98 m, the headroom may not be less than the height of the equipment
Section 1910.303(g)(1)(vi) sets minimum headroom at 1.91 m (6.25 ft) for installations built before August 13, 2007, and 1.98 m (6.5 ft) for installations built on or after August 13, 2007, except that where the electrical equipment exceeds 1.98 m (6.5 ft) in height, the minimum headroom may not be less than the height of the equipment. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(vi): 1.91 m (6.25 ft) for installations built before August 13, 2007, and 1.98 m (6.5 ft) for installations built on or after that date, except that if the equipment is taller than 1.98 m, the headroom may not be less than the height of the equipment; those substitutions fail that cited requirement.
29. For indoor equipment rated 1200 amperes or more and over 1.83 m (6.0 ft) wide that contains overcurrent, switching, or control devices, what access does 29 CFR 1910.303(g)(1)(iv) generally require?
Show answer
Answer: D. One entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high at each end of the working space, with stated exceptions for a continuous unobstructed exit or a doubled working space
Section 1910.303(g)(1)(iii) requires at least one entrance of sufficient area to the working space. For equipment rated 1200 amperes or more and over 1.83 m (6.0 ft) wide containing overcurrent, switching, or control devices, (g)(1)(iv) requires one entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high at each end of the working space, except where the location permits a continuous and unobstructed way of exit travel, or where the required working space is doubled and the entrance is set back the Table S-1 distance. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(iii)–(iv): One entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high at each end of the working space, with stated exceptions for a continuous unobstructed exit or a doubled working space; those substitutions fail that cited requirement.
30. For indoor switchboards, panelboards, distribution boards, and motor control centers, what dedicated space does 29 CFR 1910.303(g)(1)(vii)(A)(1) require above the equipment?
Show answer
Answer: D. A space equal to the width and depth of the equipment, extending from the floor to a height of 1.83 m (6.0 ft) above the equipment or to the structural ceiling, whichever is lower, dedicated to the electrical installation
Section 1910.303(g)(1)(vii) requires those boards and motor control centers to be located in dedicated spaces and protected from damage. For indoor installation, the space equal to the width and depth of the equipment and extending from the floor to a height of 1.83 m (6.0 ft) above the equipment or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. Piping, ducts, or equipment foreign to the electrical installation may not be located in this area unless isolated or protected as provided in the section. A dropped or suspended ceiling is not a structural ceiling. Choices A, B, C each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(1)(vii)(A)(1): A space equal to the width and depth of the equipment, extending from the floor to a height of 1.83 m (6.0 ft) above the equipment or to the structural ceiling, whichever is lower, dedicated to the electrical installation; those substitutions fail that cited requirement.
31. Except as otherwise required or permitted, live parts of electric equipment operating at which voltage shall be guarded against accidental contact under 29 CFR 1910.303(g)(2)?
Show answer
Answer: C. 50 volts or more, by approved cabinets or other approved enclosures, or by a listed alternative such as a room accessible only to qualified persons or elevation of 2.44 m (8.0 ft) or more
Section 1910.303(g)(2)(i) requires live parts of electric equipment operating at 50 volts or more to be guarded against accidental contact by approved cabinets or other approved enclosures, or by location in a room or vault accessible only to qualified persons; by partitions or screens that limit access to qualified persons; by placement on a suitable balcony, gallery, or platform; or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(2)(i): 50 volts or more, by approved cabinets or other approved enclosures, or by a listed alternative such as a room accessible only to qualified persons or elevation of 2.44 m (8.0 ft) or more; those substitutions fail that cited requirement.
32. What does 29 CFR 1910.303(g)(2)(iii) require at entrances to rooms and other guarded locations containing exposed live parts?
Show answer
Answer: B. Conspicuous warning signs forbidding unqualified persons to enter
Section 1910.303(g)(2)(iii) states that entrances to rooms and other guarded locations containing exposed live parts shall be marked with conspicuous warning signs forbidding unqualified persons to enter. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(g)(2)(iii): Conspicuous warning signs forbidding unqualified persons to enter; those substitutions fail that cited requirement.
33. For many outdoor electrical installations over 600 volts, what minimum fence or wall height does 29 CFR 1910.303(h)(2)(ii) require to deter access by persons who are not qualified?
Show answer
Answer: A. A fence not less than 2.13 m (7.0 ft) in height, or a combination of 1.80 m (6.0 ft) or more of fence fabric and a 305-mm (1-ft) or more extension using three or more strands of barbed wire or equivalent
Section 1910.303(h)(2)(ii) states that, for installations other than the equipment described in (h)(2)(v), a wall, screen, or fence shall be used to enclose an outdoor electrical installation to deter access by persons who are not qualified. A fence may not be less than 2.13 m (7.0 ft) in height, or a combination of 1.80 m (6.0 ft) or more of fence fabric and a 305-mm (1-ft) or more extension utilizing three or more strands of barbed wire or equivalent. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(h)(2)(ii): A fence not less than 2.13 m (7.0 ft) in height, or a combination of 1.80 m (6.0 ft) or more of fence fabric and a 305-mm (1-ft) or more extension using three or more strands of barbed wire or equivalent; those substitutions fail that cited requirement.
34. What does 29 CFR 1910.303(h)(5)(iii) require at entrances to buildings, rooms, or enclosures containing exposed live parts or exposed conductors operating at over 600 volts, nominal?
Show answer
Answer: C. The entrances shall be kept locked unless under the observation of a qualified person at all times, and permanent conspicuous warning signs shall be provided reading substantially DANGER—HIGH VOLTAGE—KEEP OUT.
Section 1910.303(h)(5)(iii) requires those entrances to be kept locked unless they are under the observation of a qualified person at all times, and requires permanent and conspicuous warning signs reading substantially as follows: DANGER—HIGH VOLTAGE—KEEP OUT. Choices A, B, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(h)(5)(iii): The entrances shall be kept locked unless under the observation of a qualified person at all times, and permanent conspicuous warning signs shall be provided reading substantially DANGER—HIGH VOLTAGE—KEEP OUT; those substitutions fail that cited requirement.
35. Where energized parts are exposed on circuits exceeding 600 volts, nominal, what minimum clear work space does 29 CFR 1910.303(h)(3) require?
Show answer
Answer: A. Not less than 1.98 m (6.5 ft) high, measured vertically from the floor or platform, and not less than 914 mm (3.0 ft) wide, measured parallel to the equipment, with depth as required in Table S-2, and adequate for a 90-degree door opening
Section 1910.303(h)(3) requires sufficient space about electric equipment for ready and safe operation and maintenance. Where energized parts are exposed, the minimum clear work space may not be less than 1.98 m (6.5 ft) high (measured vertically from the floor or platform) or less than 914 mm (3.0 ft) wide (measured parallel to the equipment). The depth shall be as required in paragraph (h)(5)(i) / Table S-2. In all cases, the work space shall be adequate to permit at least a 90-degree opening of doors or hinged panels. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(h)(3): Not less than 1.98 m (6.5 ft) high, measured vertically from the floor or platform, and not less than 914 mm (3.0 ft) wide, measured parallel to the equipment, with depth as required in Table S-2, and adequate for a 90-degree door opening; those substitutions fail that cited requirement.
36. Under Table S-2 of 29 CFR 1910.303, what is the minimum depth of clear working space for 601–2500 volts to ground under Condition A?
Show answer
Answer: B. 0.9 m (3.0 ft)
Table S-2 lists 601–2500 volts to ground as 0.9 m (3.0 ft) for Condition A, 1.2 m (4.0 ft) for Condition B, and 1.5 m (5.0 ft) for Condition C. Condition A is exposed live parts on one side and no live or grounded parts on the other side, or exposed live parts on both sides effectively guarded by suitable insulating material.
37. Where rear access is required to work on deenergized parts on the back of enclosed equipment, what minimum horizontal working space do the notes to Tables S-1 and S-2 require?
Show answer
Answer: B. 762 mm (30 in.) horizontally
Note 3 to Table S-1 and note 3 to Table S-2 both state that working space is not required in back of certain dead-front assemblies where there are no renewable or adjustable parts on the back and all connections are accessible from locations other than the back. Where rear access is required to work on deenergized parts on the back of enclosed equipment, a minimum working space of 762 mm (30 in.) horizontally shall be provided. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303 Table S-1 note 3 and Table S-2 note 3: 762 mm (30 in.) horizontally; those substitutions fail that cited requirement.
38. Where circuit breakers or fuses are applied in compliance with series combination ratings marked on the equipment by the manufacturer, what field marking does 29 CFR 1910.303(f)(5) require on the equipment enclosure?
Show answer
Answer: A. A readily visible legend stating Caution—Series Combination System Rated __ Amperes. Identified Replacement Component Required.
Section 1910.303(f)(5) requires that where circuit breakers or fuses are applied in compliance with the series combination ratings marked on the equipment by the manufacturer, the equipment enclosures shall be legibly marked in the field to indicate that the equipment has been applied with a series combination rating. The marking shall be readily visible and shall state Caution—Series Combination System Rated __ Amperes. Identified Replacement Component Required. Choices B, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(f)(5): A readily visible legend stating Caution—Series Combination System Rated __ Amperes. Identified Replacement Component Required; those substitutions fail that cited requirement.
39. How does 29 CFR 1910.303(b)(8) require electric equipment that depends on air circulation or ventilating openings to be installed?
Show answer
Answer: B. It shall be installed so that walls or adjacent equipment do not prevent airflow over exposed surfaces or through ventilating openings, and floor-mounted equipment shall have clearance above the top surfaces to dissipate rising warm air
Section 1910.303(b)(8)(ii) requires equipment that depends on natural circulation of air and convection for cooling of exposed surfaces to be installed so that room airflow over such surfaces is not prevented by walls or by adjacent installed equipment. For floor-mounted equipment, clearance between top surfaces and adjacent surfaces shall be provided to dissipate rising warm air. Section 1910.303(b)(8)(iii) requires equipment with ventilating openings to be installed so that walls or other obstructions do not prevent the free circulation of air through the equipment. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(b)(8)(ii)–(iii): It shall be installed so that walls or adjacent equipment do not prevent airflow over exposed surfaces or through ventilating openings, and floor-mounted equipment shall have clearance above the top surfaces to dissipate rising warm air; those substitutions fail that cited requirement.
40. Under 29 CFR 1910.303(c)(2), which statement about terminals is correct?
Show answer
Answer: B. Terminals for more than one conductor, and terminals used to connect aluminum, shall be so identified, and No. 10 or smaller conductors may be connected by wire-binding screws or studs and nuts having upturned lugs or equivalent
Section 1910.303(c)(2)(i) requires connections to ensure a good connection without damaging the conductors, made by pressure connectors, solder lugs, or splices to flexible leads. However, No. 10 or smaller conductors may be connected by means of wire-binding screws or studs and nuts having upturned lugs or equivalent. Section 1910.303(c)(2)(ii) requires terminals for more than one conductor, and terminals used to connect aluminum, to be so identified. Choices A, C, D each substitute a different classification, condition, value, or procedure for the rule in 29 CFR 1910.303(c)(2): Terminals for more than one conductor, and terminals used to connect aluminum, shall be so identified, and No. 10 or smaller conductors may be connected by wire-binding screws or studs and nuts having upturned lugs or equivalent; those substitutions fail that cited requirement.
Frequently asked questions
Is this an official exam?
No. These are original, unofficial practice questions written by PocketLearn. They are not released exam items. Unofficial independent study material. Consult official exam resources; not a complete exam review.
How many questions are there?
40 multiple-choice questions. Each question has an explanation.
Is it free?
Yes. You can open the practice set without an account; signing in lets you save progress and review mistakes.
Can I use it on my phone?
It opens in a mobile browser. A laptop or tablet is easier for longer sets.
More free practice tests
- CDL Air Brakes practice test
- CDL General Knowledge practice test
- CDL Combination Vehicles practice test
- CompTIA Security+ SY0-701 practice test
- NCLEX Pharmacology Fundamentals practice test
- NCLEX Pediatrics practice test
- Florida Real Estate Course I Unit 1 practice test
- Life and Health Insurance practice test
- FAA Part 107 Regulations practice test
- NCLEX Respiratory practice test
- CDL Pre-Trip Inspection practice test
- California Real Estate Salesperson Set 2 practice test
- NCLEX Pharmacology: Legal and Ethical Medication Safety practice test
- NCLEX Pharmacology: Antimicrobial Medications practice test
- Florida Real Estate Unit 3 Practice (Unofficial) practice test
- Florida Real Estate Unit 4: Relationships, Duties and Disclosure practice test
- CDL Air Brakes Practice — Set 3 practice test
- New York CDL HazMat Practice — Set 2 practice test
- CompTIA A+ Core 2 Practice Test Set 3 (Unofficial) practice test
- CDL Combination Vehicles Practice Set 2 (Unofficial) practice test
- EPA Section 608 Core Practice Test (Unofficial) practice test
- 2025 U.S. civics practice test
- Technician Class (ham radio) practice test